cable cervicom alarm screened hf cpr

Shielded cable for security systems (alarms) and intercommunication applications, when some protection against electrical noise and no halogen emission in case of fire is required.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable Cervicom Alarm Screened HF CPR
~\ImgCli\FOTO2_1802.jpg
Shielded cable for security systems (alarms) and intercommunication applications, when some protection against electrical noise and no halogen emission in case of fire is required.
Protegido electromagneticas
No propagador de la llama
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Technical characteristics
1. Operating voltage
250V
(*Not suitable for direct connection to the power supply network or other low impedance sources)
2. Test Voltage
1000 V
3. Insulation resistance
20 MOhm*Km
4. Conductor resistance
· Power (0,60mm2): 32,5 Ohm/Km
· Signal (0,20mm2 ): 108 Ohm/Km
5. Operating Tª
-15° a +70°C
6. Capacitance
110 pFm/m Aprox.
Construction
1. Conductor
Flexible bare copper wires
Cross-sectional area:
· Power: 0,60mm2
· Signal: 0,20mm2
2. Insulation
Halogen free compound
Identification:
· Power: Red, Black
· Signal: Colours (See attached table)
3. Composition
Insulated conductors laid up together
4. Outer sheath
Halogen free compound
Colour: White
5. Screen
Aluminium/polyester tape + tinned copper drain wire
Standards
1. CPR Classification (Euroclass)
Dca-s2,d2,a1
(According to UNE-EN 50575)
Standards / Properties
1. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
2. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
3. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductividad =< 10µS/mm)
4. Low smoke emission
UNE-EN 61034 (IEC 61034)