cy 500 v cable cervipar

Flexible instrumentation and control cable, shielded pairs formed together with copper braid. Suitable for applications requiring protection against electrical noise and crosstalk high

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
CY 500 V Cable Cervipar
~\ImgCli\cable_cervipar_cy_500v.jpg
Flexible instrumentation and control cable, shielded pairs formed together with copper braid. Suitable for applications requiring protection against electrical noise and crosstalk high
No propagador de la llama
Construction
1. Conductor
Copper electrolytic polishing Flexible according to UNE-EN 60228
2. Isolation
PVC type TI2 according to EN-50363-3
3. Cabling
Conductive wirings in pairs (Num same)
4. External Cover
TM2 PVC outer cover according to EN-50363.-4-1

Cover black or blue

5. Shield set
Tape of polyester + braid of copper polishing (60%)
6. Set wiring
Pairs wired in concentric layers
1. Rated voltage
300/500 V
2. Test voltage
2.000 V
3. Temperature Range
-15 ºC a 70 ºC
4. Radius of curvature
10 times the outer diameter. cable (mm)
Normative
1. Flame retardant
UNE-EN 50265-2-1 (IEC 60332-1)