Screened Cable Cerviflam RC4Z1 K 300500V CPR

Shielded flexible instrumentation and control cable, for locations where a good electromagnetic protection is necessary and and no halogen emission in case of fire is required.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Screened Cable Cerviflam RC4Z1-K 300/500V CPR
~\ImgCli\FOTO2_396.jpg
Shielded flexible instrumentation and control cable, for locations where a good electromagnetic protection is necessary and and no halogen emission in case of fire is required.
Protegido electromagneticas
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
XLPE (Cross-linked polethylene)
Identificación: HD 308 S2 (See colour table)
3. Composition
Insulated conductors laid-up together
4. Screen
Bare copper wire braid
Coverage: 60% aprox.
5. Outer sheath
Halogen free compound
Color: Green
Technical characteristics
1. Operating voltage
300/500 V
2. Test Voltage
2000 V
3. Operating Tª (conductor)
Instalación fija: -15°C to +90°C
During Installation: 0°C Minimum
Shortcut (Max. 5 seg): 250°C
4. Min. bending radius
8xD
Standards / Properties
1. Design
Special design, according EN 50288-7
2. CPR Classification (Euroclass)
Eca
(According to UNE-EN 50575)
*IMPORTANT NOTE: This information (CPR classification) must be confirmed in case of order against existing stock at that time.
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
5. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
6. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
7. Low smoke emission
UNE-EN 61034 (IEC 61034)