Armoured cable Cerviflam RZ1MAZ1 K RZ1MZ1 K 061 kV CPR

Armored power cable for transport and distribution of electrical energy in fixed installations. Suitable for indoor and outdoor installations, on air supports, in tubes or directly buried (great mechanical protection and against rodents).
Suitable for installations in public premises according to ITC-BT 28, in premises with risk of fire or explosion

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Armoured cable Cerviflam RZ1MAZ1-K / RZ1MZ1-K 0,6/1 kV CPR
~\ImgCli\FOTO2_1681.jpg
Armored power cable for transport and distribution of electrical energy in fixed installations. Suitable for indoor and outdoor installations, on air supports, in tubes or directly buried (great mechanical protection and against rodents).
Suitable for installations in public premises according to ITC-BT 28, in premises with risk of fire or explosion (ATEX zones) according to ITC-BT 29, and in general in all the locations where a safe fire behavior is required.
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Baka corrosividad gases
Anti roedores
Antideflagrantes
Enterrado directo
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
XLPE (Cross-linked polethylene)
Identification: HD 308 S2 (See attached table)
3. Composition
Insulated conductors laid up together
4. Inner sheath
Halogen free compound
5. Armour
Galvanised steel wire armour
*In case of single cores (RZ1MAZ1-K) the armour will be made of aluminium wires.
Coverage: 90% Min.
6. Outer sheath
Halogen free compound
Colour: Green
Technical characteristics
1. Operating voltage
600/1000 V
2. Test Voltage
3500 V
3. Operating Tª (conductor)
Fixed service: -15°C +90°C
During installation: 0°C Min.
Short-circuit: 250°C (5 seg. Max)
4. Min. bending radius
10xD
Standards / Properties
1. Ref. for construction/drawing
UNE 21123-4, IEC 60502-1
2. CPR Classification (Euroclass)
Cca-s1b,d1,a1
(According to UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
5. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
6. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
7. Low smoke emission
UNE-EN 61034 (IEC 61034)