cat 6 cable cervicom data uftp lshf patch flexible cpr

Flexible screened halogen-free cable for Category 6 data transmission in local area networks (LAN), suitable for the work area (computers) and panel wiring.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cat. 6 - Cable Cervicom DATA U/FTP LSHF PATCH (Flexible) CPR
~\ImgCli\FOTO2_1326.jpg
Flexible screened halogen-free cable for Category 6 data transmission in local area networks (LAN), suitable for the work area (computers) and panel wiring.
Protegido electromagneticas
No propagador de la llama
Libre halogenos
Humos baja opacidad
Baka corrosividad gases
Construction
1. Conductor
Stranded bare copper wires
Diameter: 0,42 mm (AWG27/7)
2. Insulation
FoamSkin PE (Foam polyethylene)
Diameter: 0,98 mm
3. Composition
Two insulated conductors twisted together as a pair
4. Pair Screen
Aluminium/Polyester tape in "S" shape helically applied on two pairs covering each of them individually + flexible tinned copper drain wire
5. Assembly
4 shielded pairs laid up together
6. Overall screen
-
7. Outer sheath
Halogen free compound
Colour: Grey
Standards / Properties
1. Ref. standard for drawing
EN 50173-1; EN 50288-5-2
ISO/IEC 11801; IEC 61156-6
TIA/EIA-568-C.2
2. Flame Retardant
UNE-EN 603332-1 (IEC 60332-1)
3. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
4. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
5. Low smoke emission
UNE-EN 61034 (IEC 61034)
6. CPR Classification (Euroclass)
Eca (Según norma UNE-EN 50575)