Intrinsically Safe circuits cable Cerviflam EB Z1Z1 F 300500V

Flexible instrumentation and control cable for locations where no halogen emission in case of fire is required.
Especially recommended for use in installations in potentially explosive atmospheres in Intrinsically Safe circuits (protection mode - i - ), in accordance with the specified requirements for cables in this type of installations in

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Intrinsically Safe circuits cable Cerviflam EB Z1Z1-F 300/500V
~\ImgCli\FOTO2_2096.jpg
Flexible instrumentation and control cable for locations where no halogen emission in case of fire is required.
Especially recommended for use in installations in potentially explosive atmospheres in Intrinsically Safe circuits (protection mode - i - ), in accordance with the specified requirements for cables in this type of installations in the standards IEC / EN 60079 and IEC / EN 60079-25.
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Antideflagrantes
Seguridad intrinseca
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
Halogen free compound
Identification: HD 308 S2 (See attached table)
3. Composition
Insulated conductors laid up together
4. Outer sheath
Halogen free compound
Color: Light blue
Technical characteristics
1. Operating voltage
300/500 V
2. Test Voltage
2000 V
3. Operating Tª (conductor)
Fixed installation: -15°C a +70°C
During installation: 0°C Mínimo / Short-circuit (Max. 5 seg): 160°C
4. Min. bending radius
Fixed installation: 4xD / During installation: 6xD
5. Capacitance
150 pF/m Max.
6. Inductance
1 mH/Km Max.
7. L/R ratio
25 µH/Ohm Max. (Cross sectional areas up to 1mm2, including)
40 µH/Ohm Max. (Cross sectional areas of 1,5mm2)
60 µH/Ohm Max. (Cross sectional areas of 2,5mm2)
Standards
1. Ref. for construction/drawing
Special design, based on EN 50288-7
2. Reference standards
EN 60079-14 / IEC 60079-14 / VDE 0165-1 - (Section 16.2.2)
EN 60079-25 / IEC 60079-25 / VDE 0170-10-1 (Section 9)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. CPR Classification (Euroclass)
Eca (According to UNE-EN 50575)
5. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
6. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
7. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
8. Low smoke emission
UNE-EN 61034 (IEC 61034)