nycy cable 06 1 kv

Shielded power and control cable mainly recommended for use in industrial environments where some electromagnetic protection is required. With 3 conductor configuration, specially recommended for connecting variable frequency drives. Suitable for indoor and outdoor installations, in dry or humid locations, in air or directly buried (with proper sand back filling).

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Shielded cable Cerviwire NYCY 0,6/1 kV CPR
~\ImgCli\FOTO2_1184.jpg
Shielded power and control cable mainly recommended for use in industrial environments where some electromagnetic protection is required. With 3 conductor configuration, specially recommended for connecting variable frequency drives. Suitable for indoor and outdoor installations, in dry or humid locations, in air or directly buried (with proper sand back filling). The cross sectional area of the concentric conductor is indicated in the construction data table, therefore, as long as it is in accordance with the applicable regulations in each installation, it can be used as a neutral conductor, protection conductor (ground) or simultaneously also as a screen.
Protegido electromagneticas
No propagador de la llama
Resistente UV
Enterrado directo
Construction
1. Conductor
Bare copper
· < 25mm2: Class I
· From 25mm2 (inclusive): Class II
2. Insulation
PVC (Polyvinyl chloride)
Identification: Colours according to HD 308 S2. (See attached table)
3. Composition
Insulated conductors laid up together
4. Bedding
PVC (Polyvinyl chloride)
5. Screen
Copper wires concentric conductor + counter helix copper tape
*The cross-sectional area of the screen is specified in the cable composition, after the cross sectional area of the conductors, separated by: /
6. Outer sheath
PVC UV (Polyvinyl chloride)
Colour: Black
Technical characteristics
1. Operating voltage
600/1000 V
2. Test Voltage
4000 V
3. Operating Tª (conductor)
-5°C +70ºC
Standards / Properties
1. Reference standards
VDE 0276-603
VDE 0276-627 (from 5 conductors, inclusive)
2. CPR Classification (Euroclass)
Eca
(According to UNE-EN 50575)
3. Flame Retardant
VDE 0482-332-1-2 (IEC 60332-1-2)
4. Other characteristics
UV Resistant